N2XH

XLPE/HFFR power cable with special fire performance 0,6/1 kV

Standard:

VDE 0276-604

Nominal voltage:

0,6/1 kV

Temperature application:

  • at installation: od -5°C do +50°C
  • fixed: od -30°C do +90°C

Insulation/sheath:

XLPE/HALOGEN-FREE FLAME-RETARDANT POLYOLEFIN

Construction:

  • conductor: Cu class 1 or class 2 acc. to VDE 0295 (IEC 228/HD 383), solid or stranded
  • insulation: XLPE type 2XI1 according to VDE 0276-604
  • core colours: acc. to VDE 0293 (=HD 186)
  • type -O: without yellow/green core
  • type -J: with yellow/green core
  • cores: concentrically stranded
  • filling: flame-retardant halogen-free filling
  • sheat: polyolefin type HM4 according to VDE 0276-604

Sheath colour:

black

Fire classification:

Single core sheathed (unarmoured): B2ca-s1b,d1,a1

Multicore sheathed (unarmoured) round conductor: Cca-s1b,d2,a1

Multicore sheathed (unarmoured) sector conductor: B2ca-s1b,d0,a1

Flame retardance: 

EN 60332-1-2

EN 60266-2-4

Minimal bending radius: 

multi-core – ca. 15-18x diameter

Application:

Power, distribution and control cables in industrial plants, power stations, hotels, hospitals, schools, tunnels,  data centers and other electrical plants in which high  electrical and thermal strain is expected and requires a greater degree of fire protection. For the installation on cable trays, under plaster, in masonry and in concrete. It is not suitable for direct burial without external protection against mechanical stress or water.
 

Declaration of performance

N2XH

XLPE/HFFR power cable with special fire performance 0,6/1 kV

Standard:

VDE 0276-604

Nominal voltage:

0,6/1 kV

Temperature application:

  • at installation: od -5°C do +50°C
  • fixed: od -30°C do +90°C

Insulation/sheath:

XLPE/HALOGEN-FREE FLAME-RETARDANT POLYOLEFIN

Construction:

  • conductor: Cu class 1 or class 2 acc. to VDE 0295 (IEC 228/HD 383), solid or stranded
  • insulation: XLPE type 2XI1 according to VDE 0276-604
  • core colours: acc. to VDE 0293 (=HD 186)
  • type -O: without yellow/green core
  • type -J: with yellow/green core
  • cores: concentrically stranded
  • filling: flame-retardant halogen-free filling
  • sheat: polyolefin type HM4 according to VDE 0276-604

Sheath colour:

black

Fire classification:

Single core sheathed (unarmoured): B2ca-s1b,d1,a1

Multicore sheathed (unarmoured) round conductor: Cca-s1b,d2,a1

Multicore sheathed (unarmoured) sector conductor: B2ca-s1b,d0,a1

Flame retardance: 

EN 60332-1-2

EN 60266-2-4

Minimal bending radius: 

multi-core – ca. 15-18x diameter

Application:

Power, distribution and control cables in industrial plants, power stations, hotels, hospitals, schools, tunnels,  data centers and other electrical plants in which high  electrical and thermal strain is expected and requires a greater degree of fire protection. For the installation on cable trays, under plaster, in masonry and in concrete. It is not suitable for direct burial without external protection against mechanical stress or water.